TYPICAL DIMENSIONS AND SPECIFICATIONSFOR TKC RANGE OF WATER CHILLERS
(SUBJECT TO ALTERATION WITHOUT NOTICE.)

        

 

 

Model

 

Cooling capacity at 30 º C ambient & water leaving º C     

 

 

 

Fan(s)

 

 

Compressor power input max.

 

 

Tank volume

 

 

Water flow at 150 kPa pump head

 

 

Standard pump

 

 

Current max

 

 

Dimensions width x length x height

 

 

Mass approx.

 

 

Water connections tank

In     Out

Over-flow

Make-up

6

11

16

machine

operating

TKC

 

kW

 

No. x kW - Ømm

kW

litre

m3/h

kW

A

mm

kg

  mm NB

 

15800

11.5

13.5

15.8

1 x 0.64-500

4.4

200

2

0.37

13

920x1430x1850

200

400

32

32

20

 

33000

23

29

34

2 x 0.64-500

10

300

3.9

0.37

24

920x1950x2200

500

800

32

32

20

 

52000

35

43

52

3 x 0.64-500

15

400

5.8

0.75

38

920x2460x2200

850

1250

40

40

20